10 kV Cast-Resin Dry-Type Transformer, 30-2500 kVA

Brand name: HANI
Packing Details : Wooden box with fumigation or Wooden Fram or Steel Frame
Delivery Details: 30~60days or Based on the quantity
Shipping: Sea freight、Land freight、Air freight

HANI specializes in industrial electrical automation, delivering integrated drive and control solutions to safeguard your production.

Product Details

Product overview

  • This series of cast-resin transformers is produced with advanced casting technology, giving high reliability and long service life. Protective enclosures can be added to suit different degrees of protection. The products are suitable for urban networks, shopping centres, airports, tunnels, stations, docks, high-rise buildings, hospitals, theatres and other important locations, and can be combined with prefabricated substations.
  • Coils are wound with copper wire or foil, reinforced with glass fibre, and integrally cast in epoxy resin without filler after vacuum drying and degassing, giving high mechanical strength and strong resistance to short circuit and impulse.
  • The core is stacked from high-quality grain-oriented cold-rolled silicon steel sheet using 45° fully mitred, stepped laminations, effectively reducing no-load loss and product noise.
  • The core, coils and clamping pieces are clamped with elastic elements so that the coils remain in a stable state, reducing product noise.
  • Longitudinal ventilation ducts are reserved inside the wall of the integrally cast HV and LV coils, and forced-air cooling can be fitted, which increases the rated output capacity.
  • A winding temperature controller can be fitted to monitor the winding temperature rise, automatically start and stop the cooling fans and provide fault, over-temperature alarm and over-temperature trip functions. This gives reliable overload protection for the dry-type transformer and improves operating safety.

Technical parameters

Model parameters (1 of 3)

Capacity (kVA) HV (kV) Tapping LV (kV) Vector group % Short-circuit impedance (%) No-load loss (W) Load loss (120 °C) (W) No-load current (%) Weight (kg)
30 6 6.3 6.6 10 10.5 11 ±2.5% ±5% 0.4 D yn11 Y yn0 4.0 190 710 2.0 355
50 6 6.3 6.6 10 10.5 11 ±2.5% ±5% 0.4 D yn11 Y yn0 4.0 270 1000 2.0 495
80 6 6.3 6.6 10 10.5 11 ±2.5% ±5% 0.4 D yn11 Y yn0 4.0 370 1380 1.5 565
100 6 6.3 6.6 10 10.5 11 ±2.5% ±5% 0.4 D yn11 Y yn0 4.0 400 1570 1.5 590
125 6 6.3 6.6 10 10.5 11 ±2.5% ±5% 0.4 D yn11 Y yn0 4.0 470 1850 1.3 725
160 6 6.3 6.6 10 10.5 11 ±2.5% ±5% 0.4 D yn11 Y yn0 4.0 540 2130 1.3 836
200 6 6.3 6.6 10 10.5 11 ±2×2.5% ±5% 0.4 D yn11 Y yn0 4.0 620 2530 1.1 1020
250 6 6.3 6.6 10 10.5 11 ±2×2.5% ±5% 0.4 D yn11 Y yn0 4.0 720 2760 1.1 1150
315 6 6.3 6.6 10 10.5 11 ±2×2.5% ±5% 0.4 D yn11 Y yn0 4.0 880 3470 1.0 1490
400 6 6.3 6.6 10 10.5 11 ±2×2.5% ±5% 0.4 D yn11 Y yn0 4.0 980 3990 1.0 1630
500 6 6.3 6.6 10 10.5 11 ±2×2.5% ±5% 0.4 D yn11 Y yn0 4.0 1160 4880 1.0 2050
630 6 6.3 6.6 10 10.5 11 ±2×2.5% ±5% 0.4 D yn11 Y yn0 4.0 1340 5880 0.85 2230
630 6 6.3 6.6 10 10.5 11 ±2×2.5% ±5% 0.4 D yn11 Y yn0 6.0 1300 5960 0.85 2400
800 6 6.3 6.6 10 10.5 11 ±2×2.5% ±5% 0.4 D yn11 Y yn0 6.0 1520 6960 0.85 2745
1000 6 6.3 6.6 10 10.5 11 ±2×2.5% ±5% 0.4 D yn11 Y yn0 6.0 1770 8130 0.85 3250
1250 6 6.3 6.6 10 10.5 11 ±2×2.5% ±5% 0.4 D yn11 Y yn0 6.0 2090 9690 0.85 3980
1600 6 6.3 6.6 10 10.5 11 ±2×2.5% ±5% 0.4 D yn11 Y yn0 6.0 2450 1170 0.85 4675
2000 6 6.3 6.6 10 10.5 11 ±2×2.5% ±5% 0.4 D yn11 Y yn0 6.0 3050 1440 0.70 5200
2500 6 6.3 6.6 10 10.5 11 ±2×2.5% ±5% 0.4 D yn11 Y yn0 6.0 3600 1710 0.70 6060
1600 6 6.3 6.6 10 10.5 11 ±2×2.5% ±5% 0.4 D yn11 Y yn0 8.0 2450 1290 0.85 4675
2000 6 6.3 6.6 10 10.5 11 ±2×2.5% ±5% 0.4 D yn11 Y yn0 8.0 3050 1590 0.70 5250
2500 6 6.3 6.6 10 10.5 11 ±2×2.5% ±5% 0.4 D yn11 Y yn0 8.0 3600 1880 0.70 6065

Model parameters (2 of 3)

Capacity (kVA) HV (kV) Tapping LV (kV) Vector group % Short-circuit impedance (%) No-load loss (W) Load loss (120 °C) (W) No-load current (%)
630 6 6.3 6.6 10 10.5 11 ±2×2.5% ±5% 3 3.15 6 6.3 D yn11 Yd11 Y yn0 6.0 1440 6360 1.0
800 6 6.3 6.6 10 10.5 11 ±2×2.5% ±5% 3 3.15 6 6.3 D yn11 Yd11 Y yn0 6.0 1620 7600 1.0
1000 6 6.3 6.6 10 10.5 11 ±2×2.5% ±5% 3 3.15 6 6.3 D yn11 Yd11 Y yn0 6.0 1940 8780 0.85
1250 6 6.3 6.6 10 10.5 11 ±2×2.5% ±5% 3 3.15 6 6.3 D yn11 Yd11 Y yn0 6.0 2340 10400 0.85
1600 6 6.3 6.6 10 10.5 11 ±2×2.5% ±5% 3 3.15 6 6.3 D yn11 Yd11 Y yn0 6.0 2790 12700 0.85
2000 6 6.3 6.6 10 10.5 11 ±2×2.5% ±5% 3 3.15 6 6.3 D yn11 Yd11 Y yn0 6.0 3600 15200 0.70
2500 6 6.3 6.6 10 10.5 11 ±2×2.5% ±5% 3 3.15 6 6.3 D yn11 Yd11 Y yn0 6.0 4230 17800 0.70
3150 6 6.3 6.6 10 10.5 11 ±2×2.5% ±5% 3 3.15 6 6.3 D yn11 Yd11 Y yn0 7.0 5040 20900 0.60
4000 10 10.5 11 ±2×2.5% ±5% 3 3.15 6 6.3 D yn11 Yd11 Y yn0 7.0 6030 25100 0.60
5000 10 10.5 11 ±2×2.5% ±5% 3 3.15 6 6.3 D yn11 Yd11 Y yn0 7.0 7200 29700 0.50
6300 10 10.5 11 ±2×2.5% ±5% 3 3.15 6 6.3 D yn11 Yd11 Y yn0 7.0 8500 35300 0.50

Model parameters (3 of 3)

Rated capacity kVA HV kV HV tapping range LV kV Vector group Short-circuit impedance % No-load loss W Load loss W (120 °C) No-load current %
315 6 6.3 6.6 10 10.5 11 ±4×2.5% 0.4 Dyn11Yyn0 4 990 3160 1.1
400 6 6.3 6.6 10 10.5 11 ±4×2.5% 0.4 Dyn11Yyn0 4 1120 4270 1.1
500 6 6.3 6.6 10 10.5 11 ±4×2.5% 0.4 Dyn11Yyn0 4 1290 5225 1.1
630 6 6.3 6.6 10 10.5 11 ±4×2.5% 0.4 Dyn11Yyn0 4 1490 6170 1.0
630 6 6.3 6.6 10 10.5 11 ±4×2.5% 0.4 Dyn11Yyn0 6 1440 6360 1.0
800 6 6.3 6.6 10 10.5 11 ±4×2.5% 0.4 Dyn11Yyn0 6 1710 7500 1.0
1000 6 6.3 6.6 10 10.5 11 ±4×2.5% 0.4 Dyn11Yyn0 6 1980 8780 0.85
1250 6 6.3 6.6 10 10.5 11 ±4×2.5% 0.4 Dyn11Yyn0 6 2340 10400 0.85
1600 6 6.3 6.6 10 10.5 11 ±4×2.5% 0.4 Dyn11Yyn0 6 2720 12400 0.85
2000 6 6.3 6.6 10 10.5 11 ±4×2.5% 0.4 Dyn11Yyn0 6 3420 15200 0.70
2500 6 6.3 6.6 10 10.5 11 ±4×2.5% 0.4 Dyn11Yyn0 6 3960 18100 0.70

Tell us the rated voltage, capacity, fault level and installation country, and we will confirm the build sheet, drawing set and delivery schedule for this model. E-mail [email protected] or use the quote form on this page.

At a glance

Voltage class MV
Product Type Dry-type Power Transformer
Rated Capacity 30~2500kVA

HANI is one of China’s leading professional industrial electrical automation manufacturers, providing complete drive and control solutions to customers worldwide. HANI focuses on designing and manufacturing integrated automation systems that meet the industry’s highest standards of precision, efficiency, and durability. Our engineering expertise lies in providing turnkey electrical automation projects to optimize the performance of modern industrial manufacturing plants.

Get a free quote now